ModuleM7 — Extend through documented extension points (extension strand)
After this session you canConnect an outside data feed through the API with a least-privilege credential and safe retries, and send the result outward through an authenticated webhook.
Time58 min with a facilitator · about 58 min on your own
Before you startM7-S1 (readings get a level). Larkspur Dev, Rami Aziz signed in; your terminal with Node.js 20+; BASE set to your Larkspur Dev address, as in the workbench; the CMMS stub’s address and receiver key from your enrolment message. Keep M5-S1 and M6-S1 at hand.
Go deeperWriting data · Errors and retries · Choosing a credential · Webhooks and integrations

◆ Orientation (1 min) — Both ends of the capability

Section titled “◆ Orientation (1 min) — Both ends of the capability”

The evaluator decides; now the capability needs its two ends. Readings must arrive from the plant without a person typing them, and an alarm must reach the people and systems that act on it. Both ends are documented extension points you already understand from the inside: the API with an application user, and reactions with an outbound call. What is new is doing them as a master would ship them: a credential that can do one thing, writes that are safe to repeat, and a receiver that can tell a real call from a forged one.

▤ Concept (6 min) — Least privilege, safe retries, an authenticated call

Section titled “▤ Concept (6 min) — Least privilege, safe retries, an authenticated call”

The plant’s gateway runs a small feed adapter that posts readings. It authenticates as the application user Larkspur Telemetry, whose token is the feed’s only secret. Design its access from what the feed must do, nothing more:

The feed mustSo Larkspur Telemetry gets
Create readingsAccess to one view, Telemetry intake (API), on Meter Readings, which exposes only the fields a reading needs
Find the rule that applies to a readingRead access to one view, Active rules (API), on Threshold Rules
Know each asset’s classRead access to one view, Monitored assets (API)
Nothing elseSystem level Restricted, no module or entity grant, membership of the Larkspur space only, an expiry date, a named owner

Writing through a view (POST /api/v1/v/<view id>/v1/entities/meter_readings/entries) is the narrow door you used in ACE: the view’s own access settings decide, and the call reaches only the fields the view exposes. A token that leaks can then create readings and read rules, and nothing else. The M5-S1 revocation window applies: a deactivated token keeps working for up to five minutes.

Networks fail in the middle. The hardest case is a timeout after sending: the adapter does not know whether the reading was stored. Retrying blindly would store it twice and, worse, raise a second work order. Reading back before every retry is slow. The platform gives a better tool: a unique field. Each reading carries Reading key, <sensor id>@<taken at>, and the field is unique. A repeated create is refused with 400 UNIQUE_VALUE, which the adapter treats as “already stored”. The retry policy then fits on one line per answer:

AnswerMeaningThe adapter does
2xxStoredNext reading
400 UNIQUE_VALUE on Reading keyStored earlierCount it as stored
Other 400, 422The reading is wrongLog it with the trace id and skip it
401, or the API-token refusalThe credential is refusedStop and alert; never retry
403The view’s access changedStop and alert
429, 502, 503, 504, a timeoutTransientBack off with jitter, at most five times, then park the reading

When a reading’s Level becomes Alarm, a reaction raises a work order in Asset Maintenance, and a second reaction, chained on its success, tells the CMMS with Call API. The platform does not sign outbound calls (M6-S1), so the call authenticates itself instead: the CMMS issues a receiver key, the reaction sends it in an X-Api-Key header marked Redact in history, and the CMMS checks it on every call. The body carries the work order’s number and the reading’s key, which the CMMS uses as an idempotency key: the chained reaction may run twice on the recovery path (M4-S2), and the CMMS must then ignore the second call.

flowchart LR
  G["Plant gateway: feed adapter<br/>(Larkspur Telemetry)"] -->|"POST through the intake view,<br/>unique Reading key"| R["Meter Readings"]
  R --> E["Evaluate and store level (M7-S1)"]
  E -->|"Level is Alarm"| W["Reaction: raise a work order"]
  W -->|"on success"| C["Reaction: Call API to the CMMS,<br/>key header redacted, idempotency key"]
  C --> X["CMMS checks the key,<br/>ignores a repeat"]

What to notice: there is one secret at each end, the feed’s token and the CMMS key, and neither ever appears in a record, a run history or the Function.

A body signature, an HMAC over the payload, would be stronger than a shared key, but it needs code that holds the key; on the 1.10 line a Function has no secret store, so a signature would put the key in the source. The shared key, redacted in history and rotated with the CMMS team, is the honest choice here.

⛏ Lab (41 min) — Connect the feed and close the loop

Section titled “⛏ Lab (41 min) — Connect the feed and close the loop”

Goal. Readings posted by your adapter get evaluated; an alarm raises one work order and one call to the CMMS stub; a repeated post stores nothing twice; and the feed’s token can do nothing else.

Before you start. Larkspur Dev with M7-S1’s reactions. The CMMS stub shows the requests it receives.

The credential and its doors

  1. On Meter Readings, add a unique Short Text field Reading key. Save with Save Changes.
  2. Create the view Telemetry intake (API) on Meter Readings exposing Asset, Measure, Value, Unit, Taken at, Source, Rule and Reading key, allowing creation. Create Active rules (API) on Threshold Rules (active rules only) and Monitored assets (API) on Monitored Assets, both read-only.
  3. In Administration › Organization › Users, add the application user Larkspur Telemetry, email telemetry@example.com, expiry date one year ahead, system level Restricted, member of the Larkspur space. Copy its token from the mail you receive: export TEL="<the token>".
  4. Give Larkspur Telemetry access to the three views in their access settings, and nothing else.
  5. Set export INTAKE=<intake view id> RULES=<rules view id> ASSETS=<assets view id>.

The adapter

  1. Create feed.mjs:

    const { BASE, TEL, INTAKE, RULES, ASSETS } = process.env;
    const h = { 'x-app-token': TEL, 'Content-Type': 'application/json' };
    const sleep = (ms) => new Promise((r) => setTimeout(r, ms));
    const get = async (view, entity, criteria) => {
    const q = encodeURIComponent(JSON.stringify({ limit: 50, criteria }));
    const r = await fetch(`${BASE}/api/v1/v/${view}/v3/entities/${entity}/entries?filterCriteria=${q}`, { headers: h });
    if (!r.ok) throw new Error(`lookup ${r.status}`);
    return (await r.json()).entries; // v3 reads answer {entries, tags}, without the envelope
    };
    const ruleFor = async (assetId, measure) => {
    const [asset] = await get(ASSETS, 'monitored_assets', { id: assetId });
    const rules = await get(RULES, 'threshold_rules', { 'value.asset_class.dataEntry': asset.value.asset_class.dataEntry, 'value.measure.id': measure });
    return rules[0] ?? null;
    };
    export async function post(reading) {
    const rule = await ruleFor(reading.asset.dataEntry, reading.measure);
    const value = { ...reading, measure: { id: reading.measure }, rule: rule && { dataEntity: rule.dataEntity, dataEntry: rule.id },
    reading_key: `${reading.source}@${reading.taken_at}` };
    for (let attempt = 0; attempt < 5; attempt++) {
    const r = await fetch(`${BASE}/api/v1/v/${INTAKE}/v1/entities/meter_readings/entries`, { method: 'POST', headers: h, body: JSON.stringify({ value }) });
    if (r.ok) return 'stored';
    const body = await r.json().catch(() => ({}));
    if (r.status === 400 && body.error?.code === 'UNIQUE_VALUE') return 'already stored';
    if ([429, 502, 503, 504].includes(r.status)) { await sleep(Math.random() * Math.min(60000, 1000 * 2 ** attempt)); continue; }
    if ([400, 422].includes(r.status)) return `rejected ${body.error?.code} ${body.error?.traceId}`;
    throw new Error(`stop: ${r.status} ${body.error?.code}`); // 401, 403 and anything unexpected
    }
    return 'parked';
    }
  2. Create run.mjs with five readings, using the ids of P-104 and C-220 from Monitored assets (API):

    import { post } from './feed.mjs';
    const A = (id) => ({ dataEntity: process.env.MON_ASSETS_ENTITY, dataEntry: id });
    const now = new Date().toISOString().slice(0, 16);
    const readings = [
    { asset: A(process.env.P104), measure: 'pressure', value: 8.4, unit: 'bar', source: 'PT-104-1', taken_at: `${now}:00Z` },
    { asset: A(process.env.P104), measure: 'pressure', value: 9.6, unit: 'bar', source: 'PT-104-1', taken_at: `${now}:10Z` },
    { asset: A(process.env.C220), measure: 'vibration', value: 7.9, unit: 'mm/s', source: 'VT-220-2', taken_at: `${now}:10Z` },
    { asset: A(process.env.P104), measure: 'temperature', value: 71, unit: '°C', source: 'TT-104-1', taken_at: `${now}:20Z` },
    ];
    for (const r of readings) console.log(r.source, r.taken_at, await post(r));
    console.log('repeat', await post(readings[2])); // as after a timeout: must not store twice
  3. Set P104, C220 and MON_ASSETS_ENTITY (and keep BASE exported), then run node run.mjs. Four lines say stored; the last says already stored.

Screenshot pending The terminal output of the feed run, four readings stored and the repeated one reported as already stored What to notice: the repeat is refused by the platform’s unique key and counted as stored, so a retry after a timeout cannot duplicate an alarm.

Close the loop

  1. On Meter Readings, add Raise alarm work order: On Entry Updated, watching Level, criteria Level is Alarm; Event Executor Type System; Create Data Entry in Work Orders with Title “Alarm: {Asset} {Measure} {Value} {Unit}”, Asset from the reading’s Asset, Priority High, Source “Condition Monitoring”. Save.

  2. Add Tell the CMMS of alarm: Reaction Succeeded of Raise alarm work order, Triggering Space, Call API POST to the stub’s /alarms, header X-Api-Key with the receiver key, marked Redact in history, and a payload with the work order’s number and the reading’s Reading key. Save.

  3. Run node run.mjs again (new timestamps). The readings are evaluated as before.

  4. In Work Orders, one new work order “Alarm: C-220 Vibration 7.9 mm/s”, priority High.

  5. In the CMMS stub, one POST /alarms with the work order number, the reading key and your key header. Screenshot pending The CMMS stub's request list with one POST to /alarms carrying the work order number, the reading key and the X-Api-Key header What to notice: the receiver sees the key, the run history does not; and the reading key is what lets the CMMS ignore a repeat.

  6. In Reaction Logs, the Tell the CMMS of alarm run shows X-Api-Key: ****.

  7. The repeated reading from step 7 raised no second work order: count the alarm work orders for that reading key.

Prove least privilege

  1. With $TEL, try to read suppliers through any view or directly by id: curl -s -o /dev/null -w '%{http_code}\n' "$BASE/api/v2/entities/suppliers/entries/<a supplier id>" -H "x-app-token: $TEL". It is refused.
  2. With $TEL, try to update a reading through the intake view (PATCH). It is refused: the view allows creation only.
  3. Record the token’s owner and expiry in the program’s integration register.

Check.

  • Reading key is unique and every stored reading has one.
  • Larkspur Telemetry is Restricted with access to three views only, an expiry date and an owner.
  • Four readings stored; the repeat answered “already stored” and stored nothing.
  • Exactly one alarm work order and one CMMS call per alarm reading.
  • The CMMS call carried the key, and the run history shows it as ****.
  • The telemetry token was refused for suppliers and for an update.
  • The integration register names the token’s owner and expiry.

Pass condition. A fresh run of run.mjs produces, for the alarm reading only, one work order and one CMMS call, the repeat stores nothing, and both negative tests are refused.

If something goes wrong

What you seeWhat to do
stop: 403 on the first postThe intake view’s access settings do not include Larkspur Telemetry, or the view does not allow creation.
lookup 403The rules or assets view is not shared with the telemetry user.
rejected ENTRY_VALIDATION_ERRORRead the error’s details: usually a field the view does not expose, or a category given as text instead of {id}.
The repeat says storedReading key is not unique, or the key is built differently on the two posts.
Two work orders for one alarmRaise alarm work order watches more than Level, or a second update re-set Level to Alarm; watch Level only.
The CMMS call fails with a blocked destinationThe stub address is private; use the public address from your enrolment message.
Model answer

The adapter writes only through the intake view, so the token can create readings and nothing else; it reads rules and assets through two read-only views to attach the right rule. Each reading’s Reading key is unique, so the repeated post, which simulates a retry after a timeout, is refused with UNIQUE_VALUE and counted as already stored: no second reading, no second evaluation, no second work order. The evaluator and Store level set Alarm on the vibration reading; Raise alarm work order, watching Level only, raised one work order as System across modules; its success started the Call API, which sent the receiver key in a redacted header and the reading key for the CMMS to deduplicate. The negative tests show the token’s blast radius: one create door and two read doors.

◇ Worked scenario (3 min) — The alarm storm

Section titled “◇ Worked scenario (3 min) — The alarm storm”

At 02:10 a vibration sensor on C-220 fails and reports 12 mm/s every ten seconds. By 02:40 there are 180 alarm readings, 180 work orders and 180 CMMS calls, and the CMMS team pages Larkspur’s on-call engineer. Decide at each step before you read on.

Step 1. Which part behaved wrongly? None, by its own contract: each reading was a real alarm by its rule, each work order followed from a reading, each call from a work order. The design is missing a rule: one open alarm per asset and measure.

Step 2. Where does that rule belong? Not in the Function: it would need to read work orders, which needs a credential, and it would hide a business rule in code. Not in the adapter: the plant should report what it measures. It belongs in configuration, where a planner can see and change it.

Step 3. The configuration. You add a reference field Open alarm work order on Monitored Assets’ source, written by a chained reaction when an alarm work order is raised and cleared by a reaction in Asset Maintenance when that work order is completed. Raise alarm work order gains a criterion: the asset’s Open alarm work order is empty. The second to 180th alarms are still stored and evaluated, so the evidence is complete, but they raise nothing.

Step 4. The faulty sensor. A reading the machine cannot produce (12 mm/s on a pump that never exceeds 8) should not be an alarm at all. You add an optional Plausible maximum to Threshold Rules, mapped onto the reading, and the evaluator gains one parameter, plausible_max: a value above it returns success: false with the message “implausible reading”, so no level is stored and Flag evaluation problem writes the note. No new level word is invented, and the planners own both limits.

The lesson: an extension that is correct reading by reading can still be wrong in bulk. Put the cross-record rules in configuration, where the people who own the process can see them.

✓ Practice (6 min) — Check your understanding

Section titled “✓ Practice (6 min) — Check your understanding”
PracticeChoose one answer.

The feed adapter times out after posting a reading. What should it do next?

  1. Explanation for A

    ✗ Incorrect

    Not this one: a duplicate reading would be evaluated again and could raise a second work order. See writes that are safe to retry.

  2. Explanation for B

    ✓ Correct

    Correct: the unique key turns a blind retry into a safe one; the refusal is the confirmation. See writes that are safe to retry.

  3. Explanation for C

    ✗ Incorrect

    Not this one: after a timeout the write may well have landed; skipping could lose a real alarm. See writes that are safe to retry.

Check your answer

The correct answer is B. Open the explanation under each option to see why.

PracticeChoose one answer.

A colleague proposes giving Larkspur Telemetry Edit on the Condition Monitoring module “so it can fix readings later”. What do you answer?

  1. Explanation for A

    ✓ Correct

    Correct: least privilege follows what the feed must do; a leaked token with Edit could change thresholds and rules. See the feed’s credential.

  2. Explanation for B

    ✗ Incorrect

    Not this one: a view that allows creation is the narrow door for creating records. See the feed’s credential.

  3. Explanation for C

    ✗ Incorrect

    Not this one: an expiry limits how long a leak lasts, not how much it can reach. See the feed’s credential.

Check your answer

The correct answer is A. Open the explanation under each option to see why.

PracticeChoose one answer.

The CMMS receives the same alarm twice, a second apart, after a reaction-service pod was replaced. What in this design keeps the CMMS correct?

  1. Explanation for A

    ✗ Incorrect

    Not this one: the platform does not sign outbound calls. See out through an authenticated call.

  2. Explanation for B

    ✗ Incorrect

    Not this one: the key authenticates the caller on every call; it is not single-use. See out through an authenticated call.

  3. Explanation for C

    ✓ Correct

    Correct: a chained reaction may run twice on recovery, so the receiver must deduplicate on a key the platform sends. See out through an authenticated call.

Check your answer

The correct answer is C. Open the explanation under each option to see why.

PracticeChoose one answer.

Why does Raise alarm work order watch only the field Level?

  1. Explanation for A

    ✗ Incorrect

    Not this one: a reaction can watch several fields; watching one is a design choice. See the lab’s troubleshooting.

  2. Explanation for B

    ✓ Correct

    Correct: watching only Level means only a change of level can raise a work order. See the lab’s troubleshooting.

  3. Explanation for C

    ✗ Incorrect

    Not this one: the loop guard counts repeats along a trace; it does not limit watched fields. See M4-S2: one run.

Check your answer

The correct answer is B. Open the explanation under each option to see why.

PracticeChoose one answer.

The CMMS team asks for an HMAC signature of each body instead of a shared key. On the 1.10 line, what do you explain?

  1. Explanation for A

    ✗ Incorrect

    Not this one: the platform does not sign outbound requests at all. See out through an authenticated call.

  2. Explanation for B

    ✓ Correct

    Correct: the stronger mechanism would weaken the key’s protection here; a redacted, rotated shared key is the honest choice. See out through an authenticated call.

  3. Explanation for C

    ✗ Incorrect

    Not this one: a body signature is stronger in principle; the problem is where the key would live. See out through an authenticated call.

Check your answer

The correct answer is B. Open the explanation under each option to see why.

The capability now runs end to end: readings in through one narrow door, evaluated, alarms turned into work orders and authenticated calls, every write safe to repeat. Next, M7-S3: the test that matters most. You hand the capability to Omar Haddad, a planner who writes no code, and he extends it on the web and on the phone.